# Frisko app and map knowledge for the RX910-SE21
What the vendor app (`FriskoOnline2025.apk`, decompiled with androguard, nothing run), the XML maps
and the PDFs say. **Everything here is unverified on the device** unless
[rx910-se21.md](rx910-se21.md) says so. Source tags: `PDF` = `RX910-SE21-AdresyMODBUS`, `XML` =
`RX910-SE21_v24062015.xml`, `MR208` = MR208-PC+ manual/map (another model: hints only), `APK` =
class in `com.frisko.frisko_mobile`.
## Key finding: the app has no control logic
The app is a generic Modbus viewer: every screen, scale, value name and icon comes from the XML
(`XmlHandler`, `ListDataParam`). It contains no register numbers except 4011 (`Comm_thread.STATUS_REG`),
base 4000 (`Frisko_Sterownik.ADR_BAZOWY`, only for its local array index; the wire address is the raw
register) and the XML tag set. It never reads 4221, 4222–4225, 4227, 4228, 4119 or 4129. Meanings
below therefore come from the PDF, the XML and the MR208 manual, not from code.
## Alarm: register 4011 (the app) vs 4221 (the PDF)
| Register | Source | Meaning |
|---|---|---|
| 4221 "Instalacja" | PDF | 0 = installation OK, 1 = installation fault. Binary, no bits, no codes. |
| 4011 "Status" | XML (Status screen) | Fault code, not a bit field: 0 OK, 2 Err_Tzew, 3 Err_Tco, 4 Err_Twew, 5 Err_Tcwu, 14 Err_Tpc, 15 Err_Tdz, 1003 Err_Presostat |
| 4073 "Presostat" | XML, PDF | 0 OK, 1 error (pressure switch input) |
- The app polls 4011 always, and on any non-zero value (even one not in the XML list) raises a
notification "Awaria sterownika: <number>" with sound and vibration; it repeats only when the code
changes (`Comm_thread.update_regs`, `status_error`). It never reads 4221.
- Likely mapping of names (inference from naming and the MR208 manual): `Tzew` outdoor 4065, `Tco`
buffer 4067, `Twew` indoor 4066, `Tcwu` 4069, `Tpc` pump outlet 4072, `Tdz` ground source
(4070/4071); codes 2–5, 14, 15 = sensor fault (MR208 "ErrTemp": pump off), 1003 = pressure switch
(MR208 "ErrPres": pump off; three trips in one cycle latch it until service clears it).
- MR208 also reports TmaxPC, TminDZ, dTmaxDZ shutdowns; SE21 may put them in 4011 or 4221
(unknown). 4011 is not in the PDF map. Next: log a read-only FC 3 of 4011 beside 4221 and 4073.
## Registers 4119, 4222–4225, 4228
| Reg | What is known | Source |
|---|---|---|
| 4119 `WyCHL` | Output, "0 OFF, 100 ON" like 4112–4118. "CHL" probably means cooling (the gateway calls it `output_cooling`; a guess). Not in the XML, so the app never shows it. The −14308 read means the register is not implemented on this firmware | PDF; read per rx910-se21.md |
| 4222–4225 | Not in the PDF, XML or APK. MR208 uses 4225 for TFer (a different layout, do not transfer). Gateway fixtures show 0 | none |
| 4228 `StanZB` | PDF text is cut: "0 –", "2 – zbCW" (value 1 and the text of 0 are missing from the PDF extract, also with `-raw`). "ZB" is not explained; not in the XML | PDF |
| 4227 `StanCO/CW` | 0 pc STOP, 1 pcCO, 2 pcCW, 3 pcCO/CW. Not in the XML; the app shows output icons instead | PDF |
| 4226 `Status` | 0 Ferie, 1 Tygodn (weekly), 2 Party, 3 ROZRUCH (start-up), 4 STOP, 5 Dezynf. Same list in the XML "Program pracy" with icons `program_ferie`, `program_tygodniowy`, `program_party`, `praca`, `stop`, `dezynf` | PDF, XML |
4226 is the effective state; 4140 is the chosen program (4226 can say STOP while 4140 says weekly).
Open: the gateway test fixture (real output, PR #40) shows 4226 = 0 while the settings backup has
4140 = 1 (weekly) and rx910-se21.md observed the weekly program. If 4226 really reads 0 then, the
PDF numbering may be shifted by one. Check by reading 4226 and 4140 together, then changing nothing.
## Modes and programs
| Reg | Values | Source |
|---|---|---|
| 4121 `TrybLZ` | Effective season: 0 summer, 1 winter. Read-only on the app's Status screen | PDF, XML |
| 4122 `TrypRA` | 0 R, 1 A, 2 *. Not in the XML. MR208 shows "Zima(A)" on its main screen: season plus A (automatic) or R (manual) | PDF, MR208 manual |
| 4123 `Tryb` | Season setting: 0 Lato, 1 Zima, 2 Auto (editable; backup value 2). Auto switches at 4124 `Temp progu Z/L` (5–35 °C whole, backup 18) | XML, PDF, backup |
| 4125 `Tryb pracy` | 0 STOP, 1 PRACA (editable; backup 1) | XML, PDF |
| 4140 `Prg` | 0 Ferie, 1 Tygodniowy, 2 Party (editable) | XML, PDF |
| 4141 Ferie days | 0–90 (XML). MR208: 0 = until switched back by hand | XML, MR208 manual |
| 4142 Party hours | 0–90 (XML). MR208: 0 = until switched back; counts down to the end of Party | XML, MR208 manual |
MR208 semantics (SE21 likely the same, unverified): Ferie keeps CO at the ferie target (4133) and CWU
at economy or off; Party keeps comfort for CO and CWU; weekly intervals are comfort, the rest economy.
## Economy or comfort period
- The app does not decide this. It shows the XML values only; the XML has no "period" register.
- The controller decides: weekly program intervals (4169–4176) give comfort, everything else economy
(MR208 manual, "Programy"). Ferie and Party override it as above.
- The effective targets 4201 (room), 4203 (CWU) are the answer. Inference for a UI: compare 4201
with 4131 (economy), 4132 (comfort), 4133 (ferie), and 4203 with 4143 / 4144. Ambiguous when two
setpoints are equal. 4202 (CO supply target) comes from the heating curve (4134) and is not a setpoint.
## "Heating CWU / CO" in the app
The app shows no such state. Its "Stan wyjść" screen lists outputs 4117 Pompa DZ, 4113 BUF, 4112 CO,
4118 CWU, 4116 CCW, 4114 Sprężarka (0/33/66/100), 4115 Grzałka CWU, each as an icon for 0, 1 or 100
(XML). Heating CO or CWU means output 4112 or 4118 on. 4227 is the controller's own summary of the
same thing (PDF); the app ignores it.
## How the app writes (read-only knowledge for a later milestone)
| Item | Finding | Source |
|---|---|---|
| Function codes | FC 3 read, FC 6 write one register. FC 16 exists in the code (`WRITE_REG_MULTI = 16`, `MDBwriteMulti`) but no UI path uses it | `Frisko_MDBRozkaz`, `Frisko_ModbusTCPSystem` |
| Unlock or password | None. No other frame is sent; `HasloLAN` 4129 (PDF) is never used. Matches the FC 6 test on 4143 | APK, rx910-se21.md |
| Unit id | The "slave" number set per controller in the app, in the MBAP unit byte | `Comm_thread`, `MDBsendData` |
| Scales | Value = register / 10 for format `XXX.X`; whole for `XX`. `ster_format` MZ = sign-magnitude: a negative write n is sent as 0x8000 + \|n\| | XML, `JavaToSterownik` |
| Range check | Min and max from the XML only, on the phone | XML |
| Queue | Writes go to the front of the queue (`AddPriorRozkaz`), ahead of polling | `Frisko_ModbusTCPSystem` |
| Confirmation | The reply (function, transaction id, address) is checked; no explicit read-back. The screen shows the new value after the next poll of that register | `MDBreadODP` |
| Failure | Up to 3 attempts per request, 500 ms between them; then the socket is closed and re-opened | `MBD_ERROR`, `ERROR_TIME_OUT` |
| Delay after write | 200 ms after FC 6, 300 ms after FC 16 | `run()` |
| Program selector | Circuit 4177 and day 4167 are plain writes, then the interval registers are polled; no explicit wait. MR208 map prescribes 500 ms between selecting and reading or writing | APK, MR208 map |
The XML schema also has `menu_set_adr` / `menu_set_val` (write a fixed value on opening a menu);
the SE21 XML does not use it.
## Request pacing
| Item | Value | Source |
|---|---|---|
| Pause after each request | 200 ms (300 ms after FC 16); poll thread starts after 250 ms | `Frisko_ModbusTCPSystem.run` |
| Poll list empty | 200 ms, then rebuilt: continuous polling, about 5 requests/s while a screen is open | `MDB_TIME_BREAK` |
| Timeout | 5000 ms default, user setting (2–5 digits) | `MDB_TIME_OUT`, `SterSettingsActivity` |
| Block read | Up to 28 registers per request, gaps up to 5 registers are read through | `MBD_SIZE_OPTYMAL`, `MBD_BREAK_OPTYMAL` |
| What is polled | Only the registers on the open screen, plus 4011 | `REG_DATA_STATUS`, `Comm_thread.set_reg` |
| Connections | One socket held open, up to 50 reconnect attempts | `disconnect_retries` |
The vendor documents no limit. The app's 200 ms pause is the only known pacing; our 36 registers in
5 blocks took 2.5 s (rx910-se21.md), so a 10 s cycle is far below the app's load.
## Open questions
- What are 4222–4225, and the missing values of 4228? (a read-only log over a heating cycle)
- Does 4011 exist and move on this firmware? Its relation to 4221.
- Is 4226 numbered as the PDF says (see above)?
- What does 4119 read when it is implemented, and is the register used at all?
- Meaning of 4122 value 2 ("*") and of 4126 `Uklad` (no values given).
+1 -1
View File
@@ -28,7 +28,7 @@ unless marked otherwise.
| Setpoints (F3) | 4131/4132 CO economy/comfort (5–35), 4143/4144 CWU economy/comfort (5–70) | whole °C |
| Protection | 4158 TmaxPc = 52 °C, 4149 TmaxCWU = 55, 4148 HistCWU = 5, 4146 PriorCWU = 1, 4147 heater delay = 20 | read 2026-10-23 |
Unknown: 4119 `WyCHL` reads −14308.
Unknown: 4119 `WyCHL` reads −14308. Vendor-app findings, all unverified: [app-knowledge.md](app-knowledge.md).