feat(deye): read totals, PV voltage and current, temperatures, frequency
Verified live on 2026-10-24 (read only, two dumps a minute apart): totals
are 32-bit low word first and stay above the today counters, PV V x A
matches PV W within the 0.1 A resolution, per-phase inverter power sums
to 636, battery current agrees with battery power, frequency is 49.95 Hz.
Rejected as unclear: alarm words 552-558, inverter and load currents
(scale does not fit), registers 592 and 604-607.